| Sign In | Join Free | My bjjsgy.com |
|
Place of Origin : China (Mainland)
Brand Name : ERFA
Certification : ISO9000
Model Number : ERFA-V315
MOQ : 1 unit
Price : Negotiated
Packaging Details : each piece with polly then 18pcs in a woodenbox with pallet
Delivery Time : 10 days after payment
Payment Terms : T/T
Supply Ability : 10000pcs per month
Rated Current : 2500A
Rated peak withstand current : 80KA
Weight of movable parts : 3.2kg
Storage life : 20years
Rated Operating Sequence : O-0.3S-CO-180S-CO
Contacts Limit Erosion : 3mm
Specification
| 1 | Rated Current | A | 2500 |
| 2 | Rated short-circuit breaking current | KA | 31.5 |
| 3 | Breaking operations of rated short circuit breaking current | Times | 20 |
| 4 | Rated short-time withstand current | KA | 31.5 |
| 5 | Rated duration of short-circuit | S | 4 |
| 6 | Rated peak withstand current | KA | 80 |
| 7 | Rated short -circuit making current | KA | 80 |
| 8 | Rated breaking current of single capacitor bank | A | 630 |
| 9 | Rated breaking current of back -to-back capacitor bank | A | 400 |
| 10 | Rated operating sequence | O-0.3S-CO-180S-CO | |
Mechanical data
| 1 | Weight of movable parts | Kg | 3.2 |
| 2 | Closing force due to bellow and atmosphere | N | 200±50 |
| 3 | Force required to hold contacts open at full stroke | N | 330±50 |
Mechanical requirements
| 1 | Clearance between open contacts | mm | 18±1 |
| 2 | Average opening speed(average of first 75% of contact gap) | m/s | 1.55±0.15 |
| 3 | Average closing speed(average of last 30% contact gap) | m/s | 0.7±0.2 |
| 4 | Rated added external contact final force | N | 3000±200 |
| 5 | Contact bouncing duration at closing operation | ms | ≤3 |
| 6 | Closing and opening non-simultaneity of three-phase contacts | ms | ≤1 |
| 7 | Maximum rebound during opening | mm | ≤3 |
Life
|
|
|
Fuse Combination Vacuum Interrupter With 31.5 KA Short Circuit Breaking Current Images |